Designing Reinforced Concrete Beams
Run the stress block backward to find the steel a beam needs.
Before this Lesson
Take the worked example's beam from Reinforced Concrete Beam Strength, 12 in. wide with its steel 20 in. down, and keep adding bars. Each one buys a little less moment than the last. Past about 4.3 in², it gets stranger: add 60% more steel, and the design strength rises about 2%, while the beam loses its warning before failure.
Designing a beam means choosing that steel: enough for the moment, not too much, and laid out so it fits.
From the moment to the steel
From Reinforced Concrete Beam Strength, for a singly reinforced rectangular beam:
The design strength must meet the demand, , with when . is 0.85 up to 4,000 psi, then 0.05 less for each 1,000 psi above that, down to 0.65.
Analysis hands you the bars and asks for the strength. Design hands you the moment, usually from the factored loads, and a width and depth, and asks for the bars:
If a question gives the required nominal moment instead, leave out.
The trouble is that shows up twice: once in the pull, and again inside . The Handbook gives no formula for the steel area, so you solve its two equations together. Substitute for , and you get a quadratic in , which your calculator's equation solver can handle (take the smaller root):
By hand, there's a quicker way. The lever arm is mostly , with trimming a couple of inches off. So guess the arm at , find the steel that arm needs, find the that steel makes, and correct the arm. A second round is usually enough.
Notice the minus sign. More steel means a deeper block and a shorter arm, so each added square inch buys less moment than the last.
Bar sizes go by number. Up to #8, the number is the diameter in eighths of an inch, so a #4 bar is 1/2 in. across. From #9 up, the bars run a little larger, so read them from the Handbook's bar table:
| Bar size | Diameter (in.) | Area (in²) |
|---|---|---|
| #3 | 0.375 | 0.11 |
| #4 | 0.500 | 0.20 |
| #5 | 0.625 | 0.31 |
| #6 | 0.750 | 0.44 |
| #7 | 0.875 | 0.60 |
| #8 | 1.000 | 0.79 |
| #9 | 1.128 | 1.00 |
| #10 | 1.270 | 1.27 |
| #11 | 1.410 | 1.56 |
Source: Adapted from the FE Reference Handbook, Design of Reinforced Concrete Components (ACI 318-14), ASTM Standard Reinforcement Bars
To choose bars, divide the required area by one bar's area and round the count up, never down. The most efficient arrangement is the one with the least area that's still enough, as long as the bars fit across the beam. Then confirm , because the whole calculation assumed .
When φ = 0.9 no longer applies
Every design so far assumed and then checked . A beam that needs a lot of steel can fail that check, and the Handbook sorts sections into three bands by their net tensile strain. That strain is measured at , the depth to the lowest layer of bars. With one layer, .
Source: Adapted from the FE Reference Handbook, Design of Reinforced Concrete Components (ACI 318-14), Strain Conditions. Values of φ added.
All three start from the same 0.003 at the top, where the concrete crushes. What differs is how deep the neutral axis sits, and so how far the steel has stretched by then.
- Tension-controlled, : the steel has stretched well past yield, the beam has cracked and sagged in plain sight, and .
- Compression-controlled, : that's about the yield strain of grade 60 steel, , so the steel has barely yielded, if at all, when the concrete crushes. The beam fails the way a short column does, by crushing, suddenly, and it gets a column's . The Handbook's Resistance Factors list gives 0.65 for members with tied reinforcement, and beams use the same values.
- Transition, in between: slides along a straight line, which the Handbook writes as . That's about 0.65 at 0.002 and 0.90 at 0.005, with the coefficients rounded.
Since , and shrinks above 4,000 psi, the same block depth means a deeper neutral axis in stronger concrete. Leaving at 0.85 makes too small and look better than it is.
The most steel worth using
The bands have a simple geometry. At the edge of tension-controlled, the strain line runs from 0.003 at the top to 0.005 at the steel, so it covers 0.008 over the depth . Similar triangles put the neutral axis at
which is the Handbook's label on the tension-controlled profile, . The same reasoning at 0.002 gives . That fixes , and turns it into the largest steel area that keeps the section tension-controlled:
For the beam in the Hook, 12 in. wide with in. and 4,000 psi concrete, in., in., and in². Here's what its strength does as steel goes in:
Up to 4.34 in², climbs, a little less with each square inch, as the arm shrinks. Past it, keeps climbing, but each added bar pushes the neutral axis deeper and leaves the steel less strain, so falls almost as fast. crawls from 328 to 336 ft-kip while the steel grows 60%, to 6.94 in² at the compression-controlled edge. The extra steel buys almost nothing, and it costs the beam its warning. So works as a ceiling: a beam that needs more strength than it gives needs more depth.
Every change to a section moves the neutral axis through one expression. Put into :
A larger means a deeper neutral axis, less strain left for the steel, and less warning. A smaller buys strain back.
How deep must the beam be?
Sometimes the bars are chosen and the depth is the unknown. That's easier, because nothing about is unknown anymore: the bars fix , and fixes . All that's left is the lever arm the moment needs:
For the 185 ft-kip beam with three #8 bars, kips and in. The arm must be in., so in.
But runs to the bar centers, and the beam's outline runs past them. Below the centers sit half a bar, the stirrup that wraps the bars, and the concrete cover outside the stirrup:
Here is the bar diameter. The Handbook gives no cover, stirrup size, or clear spacing between bars, so a question states them, with the cover usually measured to the stirrup. With 1.5 in. of cover and #4 stirrups, the beam above needs in., which a designer rounds up to 22 in.
The same stack runs across the beam. Inside the cover and the two stirrup legs, bars in a row need diameters and clear spaces between them:
Two rows of bars
When the bars won't fit across the beam, some go in a second row above the first, with a clear space between the rows. Now there are two depths, and they do different jobs.
The pull is the sum of every bar's pull, and it acts at their centroid. Effective depth is the far end of a lever arm, so runs to that centroid, the area-weighted average depth of all the tension steel:
Weight by area, not by bar count: a row of big bars pulls harder than a row of small ones. The second row sits higher, so comes out smaller than it would with every bar at the bottom. That lost lever arm is the price of the second row. The strain check still uses , the depth to the bottom row, because that's where the steel stretches most.
One-way slabs
A floor slab that spans one way, between parallel beams, is a very wide, shallow beam. Cut out a strip 12 in. wide, design it as a beam with in., and every answer is per foot of slab.
Slab bars are given by size and center-to-center spacing , in inches. A 12 in. strip holds bars, so the steel per foot is
where is one bar's area. #4 bars at 8 in. give in² per foot. A slab has no stirrups, so . Slab steel is light, so is small, often under an inch, and lands far above 0.005.