Tributary Areas and Load Paths

Every square foot of floor is carried by exactly one beam, and every beam by a girder or a column.

Before this Lesson

Picture a column holding up four floors of an office building. Each floor is designed for 50 pounds on every square foot, and 750 square feet of each floor is this column's to carry. That's 3,000 square feet at 50 psf, or 150 kips of live load.

The code lets you design this column for 60 kips. By the end of this Lesson, you'll know where the 750 comes from, how a load gets from a square foot of floor to the column, and why it's fair to knock off 90 kips.

Where a load goes

Set a box on a floor, and its weight has to reach the ground. It gets there by relay: each piece of the structure hands the load to whatever that piece is sitting on. So you can trace any load path by asking one question over and over. What is this sitting on?

In a typical floor, the slab sits on beams. The beams sit on girders, which are just beams that hold up other beams. Girders sit on columns, and columns stack down to the foundation.

1 2 3 4 slab girder beam column foundation
One bay of floor framing, with the slab cut back
Follow the numbers from slab to foundation. Dashed lines mark beams hidden under the slab.

Engineers draw this from above, in a framing plan. Here is the same bay, which is also the floor we'll follow through this Lesson: girders spanning 30 ft, beams spanning 25 ft between them, and a beam every 10 ft.

girder slab beam beam on column line column 10 ft 10 ft 10 ft 30 ft 25 ft
The same bay as a framing plan
Arrows show where each member hands its load.

Two details are worth noticing. The slab panels are long and narrow, so the slab behaves like a row of planks laid across the beams, bending only in the short direction. That's a one-way slab. And the beams on the column lines land right on the columns, so their load never touches a girder.

Halfway to the neighbors

Lay a plank across two joists and set a book in the middle, and each joist takes half its weight. Slide the book toward one joist, and that joist takes more. Now cover the whole plank evenly with books. Add up the shares, and each joist carries half the total, exactly as if you'd sawed the plank in two at the center and rested one half on each joist.

So for a uniform load, you can pretend every square foot goes to its nearest support, and the boundary between two beams sits halfway between them. The floor a member collects this way is its tributary area, and a beam's tributary width runs halfway to the neighbor on each side. The Handbook names tributary area without defining it, and it shows no framing plans or load paths, so this reasoning is yours to carry into the exam.

Section s s edge beam interior beam Plan L s/2 s/2 s/2 s
Tributary widths of an edge beam and an interior beam

An interior beam with spacing ss collects s/2s/2 from each side, so its tributary width is ss. An edge beam has a neighbor on only one side, so it gets s/2s/2, plus any slab that overhangs it. Multiply an area load qq by the tributary width, and you have a line load:

w=q×(tributary width)w = q \times (\text{tributary width})

The units tell the story: lb/ft² times ft is lb/ft. Problems give the live load in psf, and the slab's own weight is one of the dead loads: unit weight times thickness, with the thickness in feet. Problems usually state 150 lb/ft³ for concrete. The Handbook's Table 2, Average Mechanical Properties of Typical Engineering Materials, lists it as 0.086 lb/in³, which works out to about 149 lb/ft³.

Keep dead and live load apart as you go. They get different load factors, and only live load can be reduced.

Worked Example The line load on an interior beam
1 of 3

Our floor is a 6 in. concrete slab at 150 lb/ft³, with 15 psf of ceiling and mechanical weight and a 50 psf live load. Beams are 10 ft apart. Find the dead and live line loads on an interior beam.

From beam to girder

A uniformly loaded beam is symmetric, so each end hands off half its load: wL/2wL/2. Now look at what the girder feels. It doesn't touch the slab. It gets load only at the spots where beams land, so it sees point loads. At each spot, an interior girder gets a beam from each side, and an edge girder gets a beam from one side.

Beams land on the girder P P R = P R = P L/3 L/3 L/3 Slab rests directly on the girder w R = wL/2 R = wL/2 L
Two ways a girder gets its load

Spreading those point loads into a uniform load keeps the total right but understates the moment, so leave them as point loads. Design Moments and Shears picks up from there. A girder sees a uniform load only when a slab or deck rests directly on it.

A girder's tributary area is drawn the same way, halfway to the neighboring girders, so it's the span times the tributary width. On our floor, that's 30×25=75030 \times 25 = 750 ft². Not all of it passes through the girder, though. The beams landing on it pass along the middle 20 ft of that rectangle, 20×25=50020 \times 25 = 500 ft², and the other 250 ft² rides the column-line beams straight to the columns. So find a girder's load by following its beams, and save the full rectangle for live load reduction, coming up below.

Worked Example The girder on our floor
1 of 3

Beams carry wD=0.90w_D = 0.90 kip/ft and wL=0.50w_L = 0.50 kip/ft over 25 ft spans. They frame into both sides of a 30 ft interior girder at its third points. Find the point loads on the girder and its end reactions.

Reading any framing plan

That's everything a framing plan asks of you. For the load path, ask what each member lands on. For a tributary area, draw lines halfway to the neighbors. For a girder, look at what touches it: beams landing or a slab resting directly on it.

Checkpoint
1 of 3

A row of floor beams isn't evenly spaced. Beam B has a neighbor 6 ft to its left and another 10 ft to its right. Which shaded strip is its tributary area?

A.
B 6 ft 10 ft
B.
B 6 ft 10 ft
C.
B 6 ft 10 ft
D.
B 6 ft 10 ft

Columns collect everything above

A column's tributary area runs halfway to the next column in both directions, so it's a rectangle around the column. With bays aa by bb, an interior column gets abab. An edge column loses the half that would lie outside the building and gets ab/2ab/2. A corner column loses half in both directions and gets ab/4ab/4.

a b corner: ab/4 interior: ab edge: ab/2
Tributary areas of interior, edge, and corner columns

Here's a check that the bookkeeping holds together. An interior column on our floor has a tributary area of 30×25=75030 \times 25 = 750 ft², so at 90 psf it carries 67.5 kips of dead load per floor. Now follow the members instead. Two girders land on it with 22.5 kips apiece, and two column-line beams land on it with 11.25 kips apiece: 45+22.5=67.545 + 22.5 = 67.5 kips. Two roads, one number, because every square foot of floor gets counted exactly once on its way down.

Over several floors, a column just adds them up, through every level above the point you're checking. The roof usually has its own loads, so it gets its own line.

Worked Example The column from the Hook
1 of 3

An interior column on our 30 ft by 25 ft grid holds up four floors and a roof. Each floor has D=90D = 90 psf and L=50L = 50 psf, and the roof has D=25D = 25 psf and Lr=20L_r = 20 psf. Find the unfactored axial loads at the bottom of the column, before any live load reduction.

Not every square foot is full at once

Now the Hook's other number. The 150 kips assumes 50 psf on all 3,000 ft² at the same moment. But 50 psf is what a busy patch of office might see, and crowds gather in one place by leaving another. The bigger the area, the less likely it's all loaded at once, so the less load per square foot a member has to plan for. Only live load gets this treatment, since dead load is there all the time.

The Handbook's Live Load Reduction section gives the model, as found in ASCE 7:

L=Lo(0.25+15KLLAT)L = L_o \left( 0.25 + \frac{15}{\sqrt{K_{LL} A_T}} \right)

LL is the reduced design live load per square foot, LoL_o is the unreduced one, ATA_T is the tributary area, and KLLK_{LL} is the live load element factor. ATA_T means all the loaded floor area the member supports, so a column's ATA_T adds up every floor above it. The square root is the signature of averaging: average over 100 times as much floor, and the swings around the average shrink about tenfold.

How much floor can push on a member

So what's KLLK_{LL} doing? A tributary line is bookkeeping for a uniform load, and a real crowd doesn't respect it. Remember the book on the plank: past the halfway point, it still sends some of its weight to the far joist. So the floor that can push on a member is bigger than its tributary area. For a beam or girder, it's the two panels on either side, which is twice the tributary area. For a column, it's the four bays around it, which is four times. That's why the Handbook prints KLL=2K_{LL} = 2 for typical beams and girders and KLL=4K_{LL} = 4 for typical columns. KLLATK_{LL} A_T is the area of floor that actually influences the member, often called its influence area.

Girder: KLL = 2 influence area 2AT tributary area AT Column: KLL = 4 influence area 4AT tributary area AT
Tributary area and influence area
A girder's influence area is 2AT2A_T, and a column's is 4AT4A_T.

An edge or corner column loses tributary area and influence area in the same proportion, so it keeps KLL=4K_{LL} = 4, and an edge beam keeps KLL=2K_{LL} = 2. ASCE 7 uses other values for members with cantilevered slabs. The Handbook doesn't print those, so a question that needs one states it.

Where the discount stops and starts

The discount stops somewhere, because no amount of area makes a building empty. The Handbook prints two lower limits:

L≥0.5Lomembers supporting one floorL≥0.4Lomembers supporting two or more floors\begin{aligned} L &\ge 0.5L_o && \text{members supporting one floor} \\ L &\ge 0.4L_o && \text{members supporting two or more floors} \end{aligned}

One floor can plausibly fill up all at once. Several on the same day is a longer shot, so stacked floors get the lower limit.

0 2,000 4,000 6,000 8,000 10,000 12,000 0 0.2 0.4 0.6 0.8 1.0 1.2 KLLAT (ft2) L/Lo 400 ft2, 1.0reduction starts 3,600 ft2, 0.5 10,000 ft2, 0.4 one floor two or more floors formula alone
How the reduction grows with influence area

The Handbook stops there, and it doesn't say where reduction starts. Below KLLAT=400K_{LL} A_T = 400 ft² the factor climbs past 1, which would make the load bigger. ASCE 7 starts reduction at 400 ft², right where the factor equals 1, and it rules out or restricts reduction in some cases, such as live loads above 100 psf, assembly spaces, and parking garages. Since the Handbook prints none of this, a question that needs a threshold or an exclusion states it. Compare KLLATK_{LL} A_T with the threshold, not ATA_T alone.

Leave roof live load alone too. This formula is for floor live load, and ASCE 7's separate rule for roofs isn't in the Handbook.

On a beam or girder

Worked Example A floor beam just over the line
1 of 4

A beam on our floor spans 25 ft with beams 10 ft apart, and Lo=50L_o = 50 psf. The problem says reduction applies when KLLATK_{LL} A_T is at least 400 ft². Find the reduced live load in psf and per foot of beam.

On a column

Worked Example The column from the Hook, reduced
1 of 3

An interior column holds up four floors, with 750 ft² of tributary area on each and Lo=50L_o = 50 psf. Find the reduced live load and the total live load on the column.

Step back and look at what one 50 psf floor becomes.

One 50 psf floor, as three members see it
MemberATA_T (ft²)KLLK_{LL}KLLATK_{LL} A_T (ft²)LL (psf)
Floor beam250250046.0
Girder75021,50031.9
Column, four floors3,000412,00020.0

Each member starts over from LoL_o with its own area. The beam designs for 46.0 psf, while the girder holding up that same beam uses 31.9 psf, which brings its live point loads from 12.5 kips down to about 8 kips.

Knowing which rule applies

Checkpoint
1 of 3

Which of these members use KLL=4K_{LL} = 4? None of them supports a cantilevered slab.

A.
An interior girder
B.
An edge column
C.
A corner column
D.
An edge beam
E.
An interior column

Recap

  • Each member hands its load to what it sits on: slab, beam, girder, column, foundation. A girder sees point loads where beams land on it, and a uniform load only when a slab or deck rests on it directly.
  • A tributary area ends halfway to the neighbors, so every square foot is counted once. A line load is the area load, slab weight included, times the tributary width: ss for an interior beam, s/2s/2 for an edge beam.
  • Per floor, a column collects abab inside the building, ab/2ab/2 on an edge, and ab/4ab/4 at a corner.
  • L=Lo(0.25+15/KLLAT)L = L_o(0.25 + 15/\sqrt{K_{LL} A_T}), with KLL=2K_{LL} = 2 for beams and girders and 44 for columns, down to 0.5Lo0.5L_o for one floor and 0.4Lo0.4L_o for two or more. Any threshold comes from the question, and it applies to KLLATK_{LL} A_T.
  • Each member reduces from LoL_o with its own area. Dead load and roof live load don't get this reduction.