Hazen-Williams Head Loss
Water utilities use a friction formula built for water in real pipes.
Before this Lesson
- The Energy Equation · Fluid Mechanics
On summer evenings, when the whole neighborhood waters its lawns at once, the pressure sags at the far end of an 8 in. water main. The fix on the table is a 10 in. main, a quarter more diameter.
A quarter more diameter suggests a quarter less friction, and the bore's 56 percent more area suggests a little better. Both guesses are far too timid: the wider main loses about a third as much head. One exponent explains why.
One number for the pipe wall
In The Energy Equation, the head loss was a number the problem handed you. For a length of pipe, physics supplies it through the Handbook's Darcy-Weisbach equation, under Head Loss Due to Flow:
Its friction factor depends on the Reynolds number and the pipe's relative roughness, so finding it takes the water's viscosity and the Moody diagram. Pipe Friction does all of that, for any fluid in any pipe.
A water utility moves one fluid, at ordinary temperatures, through pipes wide enough that the flow is always turbulent. There the Reynolds number shifts only a little, and the pipe wall does most of the work. So in the early 1900s, Allen Hazen and Gardner Williams fit an equation to losses measured in real water pipes, with the wall boiled down to one number, the Hazen-Williams coefficient . There's no Reynolds number and no chart. The price is that it's a formula for water and nothing else.
is a smoothness score: the higher it is, the less head the pipe loses. That's backward from Manning's , where a higher number means a rougher channel. These are the values this Lesson's problems use:
| Pipe material | C |
|---|---|
| Plastic | 150 |
| Ductile iron | 140 |
| Concrete (regardless of age) | 130 |
| Cast iron, new | 130 |
| Cast iron, 5 yr old | 120 |
| Cast iron, 20 yr old | 100 |
| Welded steel, new | 120 |
Adapted from the FE Reference Handbook, Values of Hazen-Williams Coefficient C
The cast-iron rows show what age does. Unlined cast iron rusts from the inside into knobs called tubercles, which roughen the wall and narrow the bore. The formula keeps the pipe's original diameter, so the lower carries both effects.
Why diameter rules
Darcy-Weisbach already tells you the formula's shape. The loss goes as , and at a fixed flow the velocity goes as , so
Try it in your head. Halve the diameter and push the same flow through. The water moves four times as fast, so its velocity head is 16 times as big, and the narrower pipe has twice as much wall for each gallon to rub against. That's 32 times the loss, from half the diameter.
Hazen and Williams's measurements come out close to that. The Handbook's Circular Pipe Head Loss Equation (Head Loss Expressed in Feet) is
with and the length in feet, the flow in cfs, and the diameter in feet. Keep a diameter like 10/12 ft unrounded in your calculator, since the 4.87 power magnifies any rounding nearly fivefold. The flow's exponent is a little under 2 because a real pipe's friction factor eases off slightly as the water speeds up. (The Handbook first prints Hazen-Williams as a velocity, , in the style of Manning's equation. For a pipe flowing full, it's the same equation.)
Change one quantity, hold the rest, and everything else cancels in the ratio of the new loss to the old. The loss goes as , and nearly as . shares the flow's exponent and sits under it, so the loss really depends on : dividing by some factor costs exactly as much as multiplying the flow by it. And the diameter, at 4.87, dominates. For the Hook's main,
The wider main loses about a third as much head. The inches cancel in the ratio, so there was nothing to convert.
Gallons, psi, and the pressure form
The 4.73 has its units built in: cfs and feet. Water problems love gallons, though, so much of the work is converting the flow. The Handbook's Units and Conversion Factors table gives 1 ft³ = 7.481 gal and 1 cfs = 0.6463 million gallons per day (MGD). The rest follow from the 60 seconds in a minute and the 1,440 minutes in a day:
- 1 cfs = 7.481 × 60 = 449 gallons per minute (gpm)
- 1 MGD = 1,000,000 / 1,440 = 694 gpm
- 1 MGD = 1 / 0.6463 = 1.547 cfs
Utilities also think in pressure rather than head, so the Handbook prints a second version, its Circular Pipe Head Loss Equation (Head Loss Expressed as Pressure):
Here is the pressure loss in psi per foot of pipe, a rate rather than a total, so the drop over a length is . It's the feet form with the conversions folded into the constant, and the two agree within about half a percent. Each constant works only with its own units:
| Form | Constant | Result | Q in | D in |
|---|---|---|---|---|
| Head loss | 4.73 | ft, over the whole length | cfs | ft |
| Pressure | 4.52 | psi per ft of pipe | gpm | in. |
From The Energy Equation: in a level pipe of one diameter, the elevation and velocity heads don't change, so the whole loss comes out of the pressure, . With and 144 in.² in a ft², 1 psi is ft of water. The Handbook's conversion table prints 2.307.
If the pipe isn't level, the gauges also feel the change in elevation, and the energy equation sorts out how much of the difference is friction.
Running it backward
Many problems give you all but one of the five quantities and ask for the last. Each sits in the equation raised to a power, so the move is always the same: get the unknown's power alone on one side, then take the root. Your calculator's equation solver can also take the formula as written and solve for whichever one is missing.
The flow a main can carry
An allowable loss caps the flow. Say the steel main from the Worked Example may lose only 10 ft over its 3,000 ft. Isolate , then take the 0.54 power, since :
That's down from 3.09 cfs. The flow falls more gently than the allowable loss, because it answers to the loss only at the 0.54 power. With an allowable pressure drop instead, divide it by the length to get , and solve the pressure form the same way.
The smallest main, or the longest
The Handbook lists no standard pipe sizes, so a sizing problem gives you the choices. Solve for the diameter the allowable loss calls for,
then round up to the next size on the list. Rounding to the nearest size can land on a pipe slightly too small, and a pipe 5 percent too narrow loses 28 percent too much. You can also test the choices from the smallest up and take the first that stays within the limit. A limit per length, such as 4 ft per 1,000 ft, is just ft with ft.
Length is the easiest unknown, because the loss is proportional to it: divide the allowable loss by the loss per foot at the design flow.
C from a field test
An old main's can only be guessed from the table, so utilities measure it. They run a known flow through the main and read two pressure gauges a known distance apart. On a level main of one diameter, the pressure drop is the friction loss over that length, and the equation hands back . A value well below the table's for the pipe's material and age points to heavy tuberculation.
Pressures in Water Mains puts these losses into the energy equation to find the pressure left at a delivery point, and splits a flow between mains in parallel.