Pressures in Water Mains
The pressure at the tap is what's left of the reservoir's height after friction takes its share.
Before this Lesson
- Hazen-Williams Head Loss
- Pipe Friction · Fluid Mechanics
Screw a pressure gauge onto a fire hydrant 150 ft below the surface of the reservoir that feeds it through a mile of 12 in. main. With nothing flowing, it reads 65 psi. Then a crew opens a hydrant down the street, 1,500 gpm pours out, and the needle sinks to 54 psi and holds there.
The reservoir didn't drop, and neither did the hydrant. So where did 11 psi go?
The grade line sets the pressure
From The Energy Equation, with every loss between two points on the downstream side, so that here is the total loss:
The hydraulic grade line (HGL) traces , the level water would reach in a piezometer, and the energy line runs one velocity head above it. Both fall with friction and at fittings, and jump up at a pump. The Handbook's Minor Losses section gives the coefficients where a pipe meets a reservoir: 0.5 for a sharp entrance, 0.8 protruding, 0.1 rounded, and 1.0 for an exit.
With no water moving, nothing is lost, so the HGL is a level line at the reservoir's surface, and the pressure head is just the pipe's depth below it: 150 ft, or 150/2.31 = 65 psi. Utilities call that the static pressure.
Open the hydrant, and the main starts paying friction. The HGL still starts at the reservoir's surface, but now it slopes down and arrives at the hydrant lower. The pipe hasn't moved, so the pressure head, the HGL's height above the pipe, shrinks by . What's left is the residual pressure.
So a pressure question on a main is a question about where the HGL is. Write the energy equation from the reservoir's surface, where the pressure and velocity heads are zero, to a node in the main. The HGL there is the surface, less every loss on the way and the velocity head the water still carries:
From here on, is the pipe friction alone. The Handbook writes the entrance coefficient as ; calling it keeps it apart from Hazen-Williams . For psi, divide feet by 2.31, or multiply by 0.433, per the Handbook's conversion table. In a long main friction dwarfs the other terms, but use them when they're given.
Between two reservoirs, both surfaces drop their pressure and velocity heads, and the difference in level pays for the friction, the entrance, and the exit. That's the water-surface difference a main needs:
Over the ridge
The HGL knows nothing about the pipe's route. The reservoirs and friction set it, and the pipe may dip below it or climb above it. In a long gravity main of one diameter, with the minor losses small, friction is spread evenly along the length, so the HGL runs straight from one water surface to the other. Where the pipe climbs above it, the pressure head is negative: the water is below atmospheric pressure.
Here the HGL falls 80 ft over 10,000 ft, so at the crest, 4,000 ft along, it stands at ft. The crest is at 590 ft, so ft, or psi. Water still flows, since the total head keeps falling, as in a siphon, but a gauge at the crest reads a vacuum.
A main shouldn't run that way. Dissolved air comes out at low pressure and collects at the crest, choking the flow, and leaky joints there suck groundwater in. Nor can the pressure fall more than one atmosphere below gauge zero, 33.9 ft of water by the Handbook's conversion table; the water boils just short of that, and the column breaks. The fix is to keep the main below the HGL.
Pipes in series
A main often changes size along its route. Pipes joined end to end are in series: each carries the same flow, since water can't pile up at a reducer, and the losses add, since the water pays each pipe's toll in turn. The Handbook doesn't print this rule; it's continuity and the energy equation, one pipe at a time.
With the loss going as , the narrowest pipe usually dominates: at the same flow and , a foot of 8 in. pipe loses times as much as a foot of 12 in., so each foot of 8 in. counts as 7.2 ft of 12 in. That's the idea of an equivalent pipe, a single pipe that loses the same head at the same flow. With one throughout, a series set equals a length of a chosen diameter , or a single diameter for a chosen total length:
Both work with the diameters left in inches.
Grade lines through a series main
On a profile, each pipe in a series main draws its own stretch of grade line. The HGL's slope along a pipe is that pipe's head loss per foot, and the gap up to the energy line is that pipe's velocity head. At a fitting, the energy line steps down by the fitting's loss. Where the pipe size changes, the HGL steps by whatever keeps it one velocity head below.
Pipes in parallel
Pipes that leave one junction and meet again at another, such as a new main laid beside an old one, are in parallel.
At junction A there's one pressure, and so one HGL, whichever branch you look into, and the same goes for B. So both branches lose the same head, . The Handbook's Multipath Pipeline Problems section puts it plainly: "For pipes in parallel, the head loss is the same in each pipe." The flows add, , but the losses don't.
Think of the water choosing its path. If the big branch lost less head than the small one, more water would crowd into it until the losses evened out. So the larger, smoother branch ends up with most of the flow.
Set the two branches' Hazen-Williams losses equal, and the 4.73 cancels. Taking both sides to the 0.54 power, since and , gives
Then finishes the split, and either branch gives the common loss. For a 12 in. and an 8 in. main of equal length and , the ratio is , so the 12 in. main takes 74 percent: more than half, and more than its 69 percent share of the area, because the water in the bigger pipe also moves faster. A single pipe of the same length and replaces the pair if .
The same rules with Darcy-Weisbach
The rules come from continuity and one HGL per junction, so they hold for any friction formula. With Darcy-Weisbach and given friction factors, use the flow-rate form from Pipe Friction:
In series, add each pipe's loss, with its own . When the flow is unknown, as between two reservoirs, factor it out: . In parallel, equal losses give the split below, which follows from the Handbook's Multipath Pipeline Problems equation, written there with velocities. The exponents are 2 and 5, so a square root replaces the 0.54 power.
Junctions and loops
A city's distribution system is a grid of mains, with many paths to each house. Two rules hold it together, and the Handbook prints neither:
- Junctions: at every junction, the flow arriving equals the flow leaving, counting any demand drawn off there. That's continuity.
- Loops: around any closed loop, the head losses add to zero, counted positive where you travel with the flow and negative where you travel against it. You end where you started, at the same HGL, so the drops and climbs have to cancel.
A parallel pair is the simplest loop: out along branch 1 and back along branch 2, the rule reads , the equal-loss rule again. Big networks are solved by guessing the flows and correcting them until every loop balances, as the Hardy Cross method does, but exam questions stop at the rules and small loops.